0,5-CXKE-R, 0,5-CXFE-R, 0,5-CHKE-R, 0,5-CHFE-R

APPLICATION

Substitute cables: NCYKY, NCYKFY, NCEY, NCEFY

Signal cables with higher resistance to fire propagation according to IEC 60332-3-22, non-halogen, with low smoke density by burning according to STN IEC 61034-2 and low corrosivity of combustion gases according to STN IEC 60754-2. They have copper cores with insulation and jacket out of non-halogen materials. Cables are designated for nominal voltage 0,3/0,5 kV, for fixed and free installation in normal and humid environment (STN 33 0300). Cables can be used in environment with fire hazard and can be installed also on flammable base.

CONSTRUCTION

Pic. 1

1 Solid copper round core.

2 Conductor insulation out of cross-linked PE or on co-polymer EVA base.

3 Wrapping with Al-PET foil with tinned copper wires (only for types CXFE and CHFE).

4 Flame retardant filling cover.

5 Flame retardant PE jacket, coloured orange with labelling by agreement.

Tab. 1 Cable dimensions

Core cross-section [mm2] Insulation thickness [mm] Jacket thickness [mm] Number of cores
1 0,6 1,2 2 - 19
1,5 0,7 1,2 2 - 19
2,5 0,7 1,2 2 - 19

Tab. 2 Sectional series of produced cables

Number of cores Conductor cross-section [mm2] Cable weight [kg/km]

Cable diameter[mm](informative)

Current loading in air [A]

2 1 114 10 20
2 1,5 150 10,5 30
2 2,5 200 11,5 40
3 1 165 10,5 18
3 1,5 170 11 25
3 2,5 237 13 34
4 1 170 12,5 16
4 1,5 216 13,5 24
4 2,5 302 15 32
5 1 193 12,5 14
5 1,5 252 14 22
5 2,5 342 16 30
7 1 212 13 11
7 1,5 275 14 15
7 2,5 415 16 21
9 1 293 16 10
9 1,5 390 17,5 14
9 2,5 466 19,5 19
12 1 360 15,5 9
12 1,5 410 17 13
12 2,5 600 20,5 18
19 1 460 18,5 7
19 1,5 660 21 12
19 2,5 930 24 17

INSTALLATION AND APPLICATION PARAMETERS

  • Maximal allowed core temperature in operation 90 °C, by overload 120 °C, by short circuit 250 °C.
  • Minimal once bending radius – 6-times cable diameter.
  • Minimal allowed environment temperature for fixed installation -40 °C, for free installation -20 °C.
  • Minimal allowed environment temperature by installation (mounting) is -15 °C.

PACKING, DELIVERING, STORAGE, TRANSPORT

All cable types are supplied according to relevant company standards, twisted into coils, eventually greater lengths on wooden or metal drums. Every length is marked with tag with these data:

- producer´s mark
- cable identification
- cable length in meters
- production date
- stamp of quality control

The whole cable can be marked with description on a jacket on request of a client.

Cables can be stored in general in open-air area or in warehouses. They cannot be exposed to thermal radiation and they cannot be stored together with flammable liquids or solvents or with products containing them. It is safe to manipulate with cables at temperature range -10 °C to +50 °C.

It is necessary to assure that cables are not damaged by mechanical or other effects.