Skip to Content

JE-H(St)H-V

APPLICATION

Cables substitute: J-Y(St)Y, JE-Y(St)Y

Signal cables designated for mutual connection of sensors and evaluation centres of fire-control and security systems. Cables have higher resistance to fire propagation according to IEC 60332-3-24 (cat. C) and functional capacity by the fire for 180 minutes according to IEC 60331-23, non-halogen, with low smoke density by burning according to STN IEC 61034-2 and low corrosivity of combustion gases according to STN IEC 60754-2. They are designated for maximal voltage of 225V, for fixed installation in normal and wet ambient (STN 33 0300). Cables can be used also in environment with fire hazard and can be installed also on flammable base.

CONSTRUCTION

Pic. 1

1 Solid copper round core with diameter 0,8 mm.

2 Fireproof barrier out of mica tape.

3 Conductor insulation out of flame retardant non-halogen material. Colour marking of conductors responds to VDE 0815. Conductors are twisted into pairs. Number of pairs: 1-20.

4 Separator out of PETP tape.

5 Braiding out of temperature resistant glass tape.

6 Screening out of Al-laminated tape and min. 1 tinned copper applied wire 0,5 mm.

7 Flame retardant jacket, red colour with an option of labeling according to agreement.

Tab.1 Technical properties

Max. operating voltage [V] 220
Test voltage conductor/conductor by 50 Hz [V] 500
Test voltage conductor/screening by 50 Hz [V] 2000
Operating temperature [°C] -30 to +70
Functional capacity by fire [min] [min] 180

Tab.2 Colour marking of conductors among one group

Pair 1 2 3 4
Conductor a b a b a b a b
Colour blue red grey yellow  green brown white  black

By 2-pair cable with cross quad is:

in pair 1 colour of a-conductor blue
colour of b-conductor red

in pair 2 colour of a-conductor grey
colour of b-conductor yellow

Tab.3 Colour marking of groups

Number of group  Colour of marking tape
1. - counting red
2. - directional green
other  whitw

Tab.4 Electrical properties

Electrical core resistance, max. [Ω/km] 36,6
Insulating resistance, min. [MΩ.km] 100
Operating capacity by 800 Hz, max. [nF/km] 1201)

1) Rate by cables to 4 pairs can be exceeded by 20%.

DELIVERING, PACKING, STORAGE AND TRANSPORT

All cable types are supplied according to relevant company standards, twisted into coils, eventually greater lengths on wooden or metal drums. Every length is marked with tag with these data:

- producer´s mark
- cable identification
- cable length in meters
- production date
- stamp of quality control

The whole cable can be marked with description on a jacket on request of a client.

Cables can be stored in open-air area or in warehouses. They cannot be exposed to thermal radiation and they cannot be stored together with flammable liquids or solvents or with products containing them. It is safe to manipulate with cables at temperature range -10 °C až +50 °C.

It is necessary to assure that cables are not damaged by mechanical or other effects.