Skip to Content

JYTY

APPLICATION

Cables JYTY are designated for indoor, consistent placing of inputs of signalling, measuring, controlling and automation systems.

Cables are produced according to STN 34 7841.

MARKING EXAMPLE

JYTY 5Cx1

Cable with five Cu conductors with diameter 1mm, with colour marking of conductors type C.

CONSTRUCTION

1 Solid copper core with diameter 1 mm.

2 Insulation is out of softened PVC. Number of conductors is 2 to 24. Conductors are twisted together. Nominal thickness of insulation is stated in tab. 2. Colour marking is stated in tab. 1.

3 Core is wrapped by PET foil belt insulation.

4 Screening out of A1-PET foil with CuSn wires.

5 Grey colour PVC jacket.

Tab. 1 Colour marking of conductors according to STN 33 0165 (STN IEC 60 446)

Number of cores 2 3 4 5 multicore

Version type

 

A B D A B C D B C D C D nC nD cores
Colour of cores b gy bl b gy gy bl gy gy bl gy bl bl br outer count
br b b bg b bl b br b br b b br br other
b br b br b bl b bl b gy bl directional
b br b br b b b other
b br

(b - black, br - brown, bl - blue, gy - green-yellow)

Tab. 2 Technical properties

Nominal voltage [V] 250
Test voltage [kV] 1
Allowable operating temperature [°C] -25 to + 65
Max. effective resistance of conductor by 20 °C [Ω/km] 25
Min. insulation resistance of core by 20 °C [MΩ.km] 400

Number of elements

Nominal insulation thickness

Nominal jacket thickness 

Outer diameter*

Weight*
[mm] [mm] [mm] [kg/km]
2 0,6 1,1 6,8 56
3 0,6 1,1 7,2 70
4 0,6 1,1 8,0 85
5 0,6 1,1 9,0 102
7 0,6 1,1 9,2 126
10 0,6 1,2 10,9 177
12 0,6 1,2 11,6 205
14 0,6 1,2 12,7 234
16 0,6 1,2 13,2 260
19 0,6 1,2 13,9 300
24 0,6 1,4 16,5 386

* Informative values

PACKING, DELIVERING AND STORAGE

Cables of length 100 - 300 m are delivered in coils, eventually in drums in lengths defined by customer.

Every delivered size should have a tag with these data:
- producer`s mark
- cable identification
- cable length in meters
- production date
- stamp of quality control

Cables can be stored in open-air area or in warehouses. They cannot be exposed to thermal radiation and they cannot be stored together with flammable liquids or solvents or with products containing them. It is safe to manipulate with cables at temperature range -10 °C to +50 °C.