RHK 4
APPLICATION
Heat shrinkable combined cable outlet shapes RHK 4 are used for cores splitting before termination of plastic four-core cables AYKY or CYKY for rated voltage 0,6/1 kV.
MARKING
RHK 4 – 4/10 Outlet shape for cables cross-section from 4 x 4 mm2 up to 4 x 10 mm2
RHK 4 – 16/25 Outlet shape for cables cross-section from 4 x 16 mm2 up to 4 x 25 mm2
RHK 4 – 35/70 Outlet shape for cables cross-section from 4 x 35 mm2 up to 4 x 70 mm2
RHK 4 – 95/150 Outlet shape for cables cross-section from 3x95+70 mm2 up to 3x150+70 mm2
RHK 4 – 185/240 Outlet shape for cables cross-section from 3x185+95 mm2 up to 3x240+120 mm2
CHARACTERISTICS
Outlet shapes are made by combination of heat shrinkable tubes with hot melt adhesive on inner side and plastics moulding. In installation process only heat shrinkable tubes are shrank, which tighten cores of cable and on the other end on cylindrical part of moulding heat shrinkable tube tights the cable jacket. Plastic moulding is not shrinkable, it remains in initial stage.
Heat shrinkable tubes are made from cross-linked PE, plastic moulding from co-polymer PP.

Tab. 1. Properties of material (cross-linked PE)
| Properties of material | Tubes | Moulded pieces |
| Tensile strength [MPa] | min. 13 | min. 22 |
| Elongation at break [%] | min. 350 | min. 650 |
| Shrink temperature [°C] | 150 - 200 | - |
| Operating temperature – long term [°C] | 100 | 110 |
| Operating temperature – short term [°C] | 150 | 160 |
| Volume resisivity [W.m] | 1013 | 1016 |
| Dielectric strength [kV/mm] | 12 |
18 |
Tab. 2. Dimension table of shapes according to Pic. 1 and 2
|
Shape |
Delivered form | After free shrinking | ||||
| D1 [mm] | d1 [mm] | L1 [mm] | D2 [mm] | d2 [mm] | L2 [mm] | |
| RHK 4 – 4/10 | 23,5 | 6,5 | 120 | 10 | 3 | 110 |
| RHK 4 – 16/25 | 37 | 10 | 170 | 16 | 4 | 160 |
| RHK 4 – 35/70 | 46 | 15 | 190 | 18 | 5 | 170 |
| RHK 4 – 95/150 | 74 | 25 | 280 | 32 | 10 | 260 |
| RHK 4 – 185/240 | 95 | 33,5 | 360 | 42 | 16 | 340 |
Pic. 1. Delivered form

Pic. 2. After free shrinking