RHK 4

APPLICATION

Heat shrinkable combined cable outlet shapes RHK 4 are used for cores splitting before termination of plastic four-core cables AYKY or CYKY for rated voltage 0,6/1 kV.

MARKING

RHK 4 – 4/10 Outlet shape for cables cross-section from 4 x 4 mm2 up to 4 x 10 mm2
RHK 4 – 16/25 Outlet shape for cables cross-section from 4 x 16 mm2 up to 4 x 25 mm2
RHK 4 – 35/70 Outlet shape for cables cross-section from 4 x 35 mm2 up to 4 x 70 mm2
RHK 4 – 95/150 Outlet shape for cables cross-section from 3x95+70 mm2 up to 3x150+70 mm2
RHK 4 – 185/240 Outlet shape for cables cross-section from 3x185+95 mm2 up to 3x240+120 mm2

CHARACTERISTICS

Outlet shapes are made by combination of heat shrinkable tubes with hot melt adhesive on inner side and plastics moulding. In installation process only heat shrinkable tubes are shrank, which tighten cores of cable and on the other end on cylindrical part of moulding heat shrinkable tube tights the cable jacket. Plastic moulding is not shrinkable, it remains in initial stage.
Heat shrinkable tubes are made from cross-linked PE, plastic moulding from co-polymer PP.

Tab. 1. Properties of material (cross-linked PE)

Properties of material Tubes Moulded pieces
Tensile strength [MPa] min. 13 min. 22
Elongation at break [%] min. 350 min. 650
Shrink temperature [°C] 150 - 200 -
Operating temperature – long term [°C] 100 110
Operating temperature – short term [°C] 150 160
Volume resisivity [W.m] 1013 1016
Dielectric strength [kV/mm] 12

18

Tab. 2. Dimension table of shapes according to Pic. 1 and 2

Shape

Delivered form After free shrinking
D1 [mm] d1 [mm] L1 [mm] D2 [mm] d2 [mm] L2 [mm]
RHK 4 – 4/10 23,5 6,5 120 10 3 110
RHK 4 – 16/25 37 10 170 16 4 160
RHK 4 – 35/70 46 15 190 18 5 170
RHK 4 – 95/150 74 25 280 32 10 260
RHK 4 – 185/240 95 33,5 360 42 16 340

Pic. 1. Delivered form

Pic. 2. After free shrinking